GEA Groovy Cooling - Technical Data

A great idea in technical detail


The latest in know-how and experience, powered by the exact understanding of the users’ processes, lead to a unique technology that meets the industry’s requirements in every aspect.

The principle

  • Reduction of the dead zone behind the tubes
  • Top view of a Four Rows bundle equipped with 1'' Tube OD
  • Flow field coloured by the air velority (m/s)

The advantages

  • Inreased total heat transfer up to 20%
  • No effect on fouling characteristics
  • Higher mechanical resistance

Thermal tests: Small scale prototypes and wind tunnel tests

Comparison of external heat transfer coefficient related to the bare tube surface, with regards to the fan consumption for a four tube row bundle equipped with standard and groovy fins with a pitch of 10 and 11 FPI and tubes of 1.25 in. outside diameter.

  • Heat transfer increase on air side up to 25% at equivalent power consumption
  • Up to 20% global performance increase according to the product

Fouling

  • Comparative measurements in wind tunnel tests:
    dust spray in greasy environment onto a small scale prototype
  • Comparison to plain finned tubes prototypes
  • Increase of the pressure drop with dust content for a front velocity of 3m/s
  • The effect of the grooves is negligible

Cleaning

Cleaning of the small scale prototypes performed using conventional machines used to clean ACHE in plants, at a pressure of 80 bar. Validation: comparison between the pressure losses at different frontal velocities from non-fouled bundles and bundles cleaned after fouling.

  • No pressure drop difference measured: the groovy fin bundles were perfectly cleaned.

   

Mechanics

  • Increased mechanical resistance with Groovy Fins
  • Tests performed with 100 kg per tube
  • Increased resistance of the finned tube with the groovy fin technology
  • Only a few fins distorted, whereas the conventional fins are damaged forever