GEA Heat Exchangers / Global

2H PLASdek® Counter-Flow Cooling Tower Fills

Different types for all requirements – available in PVC and PP

From small cooling towers to large cell and natural draught cooling towers: Our PLASdek® packings fulfill all requirements. Different types of film fills with large specific surface are highly suited for clean and medium water qualities, whereas for special operation conditions and for strongly polluted water grid structures are the best choice. Ask our experts. They have long time experience and will be grateful to help you choose the right fill for your application.

  • Cooling Fills KFP 312 – Highly efficient with large specific surface, for clean cooling water
  • Cooling Fill KFP 319 – Highly efficient with large specific surface, for clean cooling water
  • Low fouling fills KFP 327, for slightly and medium polluted water
  • Low fouling fills KVP 323, for slightly and medium polluted water
  • Low fouling fills KGP 320, for slightly and medium polluted water
  • Trickle Grid Fill NET 150 - Easy to clean, for special operation conditions, for strongly polluted water
  • Splash Cooling Fill FC70.34 - Easy to clean, for special operation conditions, for strongly polluted water
  • Splash Cooling Fill FC20.30 - Easy to clean, for special operation conditions, for strongly polluted water
  • Made of PVC, large specific surface, for clean cooling water

Overview: PLASdek® Cooling Fills made of Polypropylene

Highly efficient with large specific surface, suited for clean cooling water

Highly efficient with large specific surface, suited for clean cooling water

 
KPP 312
KZP 312
KFP 319
Contact surface [m²/m³]
232
240
150
Corrugation height [mm]
12
12
19
Channels
Cross-fluted
Cross-fluted
Cross-fluted

Low fouling fills, for slightly and medium polluted water

Low fouling fills, for slightly and medium polluted water

 
KVP 319
KGP 320
KBP 320
KVP 323
KFP 327
Contact surface [m²/m³]
144
142
142
125
125
Corrugation height [mm]
19
20
20
23
27
Channels
Vertical flow
Vertical flow / off set
Vertical flow / off set
Vertical flow
Cross-fluted

Easy to clean, for special operation conditions, for strongly polluted water

Easy to clean, for special operation conditions, for strongly polluted water

 
NET25 150
FC20.30
KFP 638
FC70.34
Contact surface [m²/m³]
up to 130
110
70
94
Corrugation height [mm]
20
30
38
34
Channels
Grid / diagonal
Cross-fluted
Cross-fluted
Grid / horizontal

Overview: PLASdek® Cooling Fills made of PVC

Highly efficient with large specific surface, suited for clean cooling water

Highly efficient with large specific surface, suited for clean cooling water

 
KZC 312
KPC 312
KFC 319
Contact surface [m²/m³]
240
232
150
Corrugation height [mm]
12
12
19
Channles
Cross-fluted
Cross-fluted
Cross-fluted

Low fouling fills, for slightly and medium polluted water

Low fouling fills, for slightly and medium polluted water

 
KVC 319
KGC 320
KBC 320
KFC 327
Contact surface [m²/m³]
144
142
142
125
Corrugation height [mm]
19
20
20
27
Channels
Vertical flow
Vertical flow
Vertical flow / off set
Cross-fluted

General Technical Data of 2H PLASdek® Fills

General Technical Data of 2H PLASdek® Fills

 
PP
PVC
Void ratio [%]

> 97

Length max [mm]

2400

Width max [mm]

600

Standard height [mm]

300 or 600

Continuous operation temperature [°C]
80
55
Max. operation temperature (short term) [°C]
90
60

Maximum application temperature:

The operational temperature should be measured at the inlet pipe of the system and should not exceed the maximum temperature stated above.

High temperature applications:

Fill media in high temperature in PP (up to 100°C) available on request.

Flammability:

Products in flame retardant version according to American (ASTM E84, UL 94) and European standards (DIN 4102, NF P 92-501) are available on request. National regulations on fire protection should be taken into consideration before choosing a product.

Cross-fluted Fills

 
KPP 312
KPC 312
KZP 312
KZC 312
KFP 319
KFC 319
KFP 327
KFC 327
KFP 638
KFC 638
Contact surface [m²/m³]
232
240
150
125
70
Void ratio [%]
> 97
> 97
> 97
> 97
> 97
Corrugation height
12
12
19
27
38
Note
KFP/KGP/KVP/KBP = Fills in PP
KFC/KGC/KVC/KBC = Fills in PVC

Vertical Flow Fills

 
KVP 319
KVC 319
KGP 320
KGC 320
KBP 320
KBC 320
KVP 323
KVC 323
Contact surface [m²/m³]
144
142
142
125
Void ratio [%]
> 97
> 97
> 97
> 97
Corrugation height
19
20
20
23
Note
KFP/KGP/KVP/KBP = Fills in PP
KFC/KGC/KVC/KBC = Fills in PVC

Splash Cooling Fills

 
FC20.30
FC70.34
Contact surface [m²/m³]
110
94
Void ratio [%]
> 95
> 93
Corrugation height
30
34
Note
Our splash cooling fills are made of PP

Trickle Grid Fills

 
NET25 150
Contact surface [m²/m³]
up to 130
Void ratio [%]
> 97
Corrugation height
20
Note
Our trickle grid fills are made of PP